Three-phase AC 50Hz outdoor high-voltage switchgear, used in the 10kV electrical power systems of rural power grid and urban power grid as opening and closing load current, overload current, and short circuit current, and in other similar applications.
Working environment conditions:
1.1 Ambient air temperature: Max. temperature: +45°C; Min. temperature: -40°C; Max. daily temperature difference: 25K;
1.2 Relative humidity: Daily mean is not greater than 95%, and monthly mean is not greater than 90%;
1.3 Altitude: Not exceed 2,000 meters;
1.4 Wind: Not exceed 35m/s (equivalent to air pressure 700Pa);
1.5 Pollution degree 4;
1.6 Radial thickness of ice: 10mm;
1.7 Earthquake resistance: horizontal acceleration: 0.3g/s2; vertical acceleration: 0.2g/s2;
1.8 Installed in places free of fire, explosion, chemical corrosion and frequent severe vibration. Please contact the manufacturer for customizing those failed to follow the normal working conditions.
Rated frequency | Hz | 50 | |||
Rated insulation level | Power frequency withstand voltage for 1 minute | Dry test | kV | P/phase to phase, P/phase to earth: 42 O/open contacts: 48 | |
Wet test | 34 | ||||
Lightning impulse withstand voltage (peak) | P/phase to phase, P/phase to earth: 75 O/open contacts: 85 | ||||
Rated circuit-breaker breaking current | kA | 20 | 25 | ||
Rated short-circuit making current (peak) | kA | 50 | 63 | ||
Rated peak withstand current | kA | 50 | 63 | ||
4s thermal stability current | kA | 20 | 25 | ||
Rated operating sequence | O-0.3s-CO-180s-CO | ||||
Closing time | ms | ≤50 | |||
Opening time | ≤45 | ||||
Rated short-circuit breaking current ON/ | Times | 30 | |||
OFF times | |||||
Mechanical life | 10,000 | ||||
Control circuit and auxiliary circuit, power frequency withstand voltage for 1 minute | V | 2000 | |||
Rated operating voltage and auxiliary voltage | AC/DC220、DC110/48/24 | ||||
Rated current of overcurrent trip coil | A | 5 | |||
Allowable wear thickness of dynamic and static contacts in arc extinguish chamber | mm | 3 | |||
SF6 gas pressure in box (gauge pressure) | MPa | 0 |
1.1 Suitable for three-phase AC 50Hz, 35kV power system for ...
ZN63A-24 indoor high voltage AC vacuum circuit breaker (here...
1.1 Suitable for switching various loads with different prop...
1.1 The three-phase AC 50Hz outdoor switchgear is suitable f...
1.1 Suitable for three-phase AC 50Hz, 24kV power system for ...